Architect Specifications
| 1 | General | ||||||||||||||||||||
| 1.01 | System Description | ||||||||||||||||||||
| A. | Manufactured steel embedded CMU | ||||||||||||||||||||
| B. | .1875" (3/16") Steel plate in one or more faces with 2 mil red oxide coating. | ||||||||||||||||||||
| 1.02 | Related Section | ||||||||||||||||||||
| A. | Section 5090 Metal Fastening. | ||||||||||||||||||||
| 1.03 | System Performance Requirements | ||||||||||||||||||||
| A. | Provide unit masonry complying with ASTM C-90. | ||||||||||||||||||||
| B. | Embedded block steel plate must pass static strength pullout test at 6,000 pounds minimum. | ||||||||||||||||||||
| C. | Embedded block steel plate must pass cyclical fatigue arm load test applied at load sequence 0 to 400 to 0 lbs. for 60,000 cycles, then 0 to 500 to 0 lbs. for 40,000 cycles. | ||||||||||||||||||||
| D. | Embedded block must pass ultimate load test of 2,600 lbs. | ||||||||||||||||||||
| 1.04 | Delivery, Storage and Handling | ||||||||||||||||||||
| A. | Units must be stored on covered pallets, labeled with product identification, for protection. | ||||||||||||||||||||
| 2 | Production | ||||||||||||||||||||
| 2.01 | Manufacturer | ||||||||||||||||||||
| A. | M/BED BLOCK SYSTEMS, LLC. 7508 Bull Run Drive St. Louis, MO 63123-1905 (314) 570-3008 Fax: (314) 843-1079 | ||||||||||||||||||||
| 2.02 | Materials | ||||||||||||||||||||
| A. | M/BED Concrete Masonry Units with trademark stamped on 3/16" steel plate. | ||||||||||||||||||||
| B. | Normal CMU. | ||||||||||||||||||||
| 2.03 | Size | ||||||||||||||||||||
| A. | Steel plates 7-5/8" x 7-5/8" or 7-5/8" x 15-5/8". | ||||||||||||||||||||
| B. | CMU provided 8" x 8" x 16" nominal (6", 8" and 12" available with manufacturers approval) | ||||||||||||||||||||
| 2.04 | Quality Control | ||||||||||||||||||||
| A. | Test reports by Southwest Research Institute. | ||||||||||||||||||||
| 3 | Execution | ||||||||||||||||||||
| 3.01 | Installation | ||||||||||||||||||||
| A. | Install M/BED unit as detailed on shop drawings provided by the steel erector, per standard masonry practice. | ||||||||||||||||||||
| B. | Any M/BED CMU alterations must be approved by the factory. | ||||||||||||||||||||
| 3.02 | Cleaning | ||||||||||||||||||||
| A. | Clean wall daily with brush as required. | ||||||||||||||||||||